Ali Abed Al jabar Homoush |
Abstract |
The main object of this research is to make an experimental study to clarify the effect of water to air flow ratio and the inlet water temperature (tw1) On the thermal performance of a cooling tower. The experiments were made for different values of water to air flow ratio and they were 0.6, 0.8, and 1.2. The temperatures of the inlet water were in the range [30-50] °C. The experimental study showed that increasing the water to air flow ratio will reduce the cooling tower performance, whereas increasing the inlet water temperature until 40°C will increase the cooling tower performance and then its performance is decreasing at higher temperatures. This clarified by water temperature curves, relative humidity and dry bulb temperature of the air and by calculating the cooling tower range and efficiency.
Keywords: cooling towers, tower efficiency- tower range, flow rate temperature |
الكاتب |
علي عبد الجبار حمش |
الملخص |
إن الهدف الرئيسي من هذا البحث هو إجراء دراسة تجريبية لتوضيح تأثير كل من نسبة تدفق الماء إلى تدفق الهواء ودرجة حرارة الماء الداخل إلى البرج (tw1) على الفعالية الحرارية لبرج التبريد . تم إجراء التجارب عند قيم مختلفة لنسبة تدفق الماء إلى تدفق الهواء وكانت على التوالي 6. 0، 8. 0 ، 1.2 أوعند قيم لدرجات حرارة الماء الداخل إلى البرج تراوحت ضمن المجال [C° [ 30- 50 . أظهرت الدراسة التجريبية بأن زيادة نسبة تدفق الماء إلى تدفق الهواء تؤدي إلى انخفاض أداء البرج ، بينما زيادة درجة حرارة الماء الداخل حتى درجة الحرارة C°40 تؤدي إلى تحسين أداء البرج حيث يبدأ أداء البرج بالانخفاض عند درجات الحرارة الأعلى من ذلك . وقد تم توضيح أداء البرج من خلال منحنيات تغير درجة حرارة الماء ، منحنيات تغير درجة حرارة ورطوبة الهواء ضمن الحشوة ومن خلال حساب فعالية و مجال البرج .
الكلمات المفتاحية: أبراج التبريد - فعالية البرج - مجال البرج - نسبة التدفق – درجة الحرارة |
Alfurat University @ 2024 by SyrianMonster | All Rights Reserved